WARNING
Moving parts hazard
Turn off electric power before servicing
this component.
Fan can start automatically.
Failure to do so can result in property
damage, personal Injury and/or death.
Indoor Air Flow Data
Indoor air flow may be determined by measuring the exter-
nal static pressure (ESP) of the duct system using an
inclined manometer or magnehelic gauge, then consulting
chart "A" to determine actual air flow.
correction multipliers contained in chart "B" to determine
accurate air flow under the listed conditions.
circumstances
should
operated at an external static pressure in excess of .30"
W.C. Operation of the Vert-I-Pak under these conditions
will result in inadequate air flow leading to poor
performance and/or premature component failure.
For LOW speed operation, connect the fan output terminal
from the thermostat to the GL terminal of the electronic
control. For HIGH speed operation, connect the fan output
terminal from the thermostat to the GH terminal of the
electronic control.
For thermostats with two-speed fan
capabilities, connect the LOW speed output to the GL
terminal, and the HIGH speed output to the GH terminal.
Determining the Indoor CFM: Char t A – CFM
VEA09
Fan Speed
Low
High
ESP (")
.10"
405
450
.15"
375
420
.20"
345
385
.25"
325
365
.30"
305
340
ESP = external static pressure in inches water column
Rated CFM at Low Speed:
VEA09/VHA09....325
VHA12/VEA12....390
VEA18/VHA18....400
For single speed thermostats connect to the GL terminal for Low speed or GH
terminal for High speed. Two speed control thermostats will use both terminals.
Use the air flow
Under no
the Vert-I-Pak equipment
Model
VHA09/VEA12/VHA12
VEA18/VHA18
Low
High
Low
CFM
420
450
405
425
385
400
355
375
320
350
be
Chassis Installation
Install the following components
A. Ensure that the wall plenum is installed in accordance
B. Place the chassis into the closet with the outdoor side
C. Slide the chassis into the wall plenum until the plenum
Figure 13
Chassis Installation/
High
Installed View
400
480
The Vert-I-Pak chassis must be inserted into the wall
375
465
350
450
plenum so that the plenum divider gasket makes
330
390
310
330
contact with the plastic condenser baffle on t he unit.
The chassis will fit approximately 2 ⅜" into the wall
plenum.
CAUTION
Excessive Weight Hazard
Use two or more people when installing
your air conditioner.
Failure to do so can result in back or
other injury
CAUTION
Cut/Sever Hazard
Some edges may be sharp, use gloves
or other hand protection when handling
unit.
Failure to do so can result in minor to
moderate personal injury.
with the instructions listed on Pages 6-10.
facing the wall plenum opening.
divider seal is established. (See Figure 13)
12