- SECURITY ONE UNINTERRUPTIBLE POWER MANAGER
Configuration Manager
Configuration Manager provides control over important operation parameters of the UPM. Configuration
Manager controls these parameters through the settings on the DIP (dual inline pin) switch pack on the rear
panel and also through certain selections accessed by Communications Manager software.
Operating Voltage: The DIP switches can be used to configure the UPM operating voltage. For North
American models, the UPM can be configured to operate at 100, 110, 115, or 120 volts. International
models can be configured for 220, 230, or 240 volts. The following table illustrates the required switch
settings for each selection.
Voltage Required
100V/208V
110V/220V
120/230V
127/240V
If Communications Manager software is installed on the host PC, Configuration Manager can use it to adjust
both Low Voltage Transfer Point and High Voltage Transfer Point. The following table provides the
allowable set points for adjusting transfer voltage (key in all three numbers shown).
Low Voltage Transfer Points (key in all three numbers)
Model
North American
International
High Voltage Transfer Points (key in all three numbers)
Model
North American
International
Low Battery Warning Time: Low battery warning time can be configured for either two or five minutes
before UPM shutdown depending on the requirements of the application. It should be noted that these times
SW#1
SW #2
SW #3
On
Off
Off
Off
On
Off
Off
Off
On
Off
Off
Off
Set Pt.
Set Pt.
Set Pt.
Set Pt.
1
2
3
089
091
093
176
181
186
Set Pt.
Set Pt.
Set Pt.
Set Pt.
1
2
3
141
145
148
282
290
296
11
SW #4
Off
Off
Off
On
4
096
192
4
151
302

Publicité