7. MultiPlus
MultiPlus 3kVA or more
For more info on how to configure the MultiPlus to work with the Smart BMS
CL 12-100 please refer to the document on our website:
https://www.victronenergy.com/upload/documents/Manual-Connecting-other-
lithium-battery-systems-to-Multis-and-Quattros-EN.pdf
The Load Disconnect and Charge Disconnect Outputs will be wired to the
MultiPlus with two inverting remote on-off cables (article number
ASS030550100) as shown in figure 4 above.
MultiPlus 500VA – 1600VA & MultiPlus Compact 800VA – 2kVA
These MultiPlus models can be controlled from the Load Disconnect and
Charge Disconnect outputs by using the BMS CL 12-200 to MultiPlus cable
(article number ASS070200100). This cable must be wired to the remote
on/off connector of the MultiPlus (connect the black wire to the ON terminal
and the red wire to the (+) terminal).
Both the Load Disconnect and Charge Disconnect outputs of the BMS must
be in 'High' state in order for the MultiPlus to operate. After shutdown due to
low battery voltage, run the alternator or use a battery charger on the primary
side of the BMS to reset the system. The MultiPlus will then switch on and
start charging (if connected to an AC power source).
14