5. GENERAL CHARACTERISTICS
Technical characteristics of communication:
. Ethernet specification compliance: IEEE 802.3 , EIA RS485
. Interface Ethernet: RJ45 10/100Mb
Default configuration:
. IP Address: 192.168.1.100
. Subnet Mask: 255.255.255.0
. Gateway: 198.168.1.1
Web pages access:
. Access to the web Servers pages and data is secured by two
identification codes (PIN and PUK codes).
. Four types of "default" users are configured:
User
administrator
99999
greenUp
88888
Installer
55555
user
11111
Note: The home page ("home") will be different depending on the
type of user that access to the device
.
manual)
Historical of consumptions
. All energy, water and gas values (Δ of consumptions and global
counters) and statistical values (average values, peak values, etc.),
only if available on the device making the measurement, are saved
automatically in files ".CSV" compatibles with Excel or "csv" reader.
. Access to this data is possible in several ways:
- "FTP" protocol
- creation of a network drive
- data download via web pages
- receive automatic reports sent by the web server
(for more details refer to the user manual)
Data storage time:
. Energies (Ea+), Water consumption, Gas Consumption: data
storage time is unlimited.
Sampling of data (accuracy per minutes) is over time reduced, thus
passing to an accuracy per hour → per day → per month → per year
for the oldest stored data.
. For data such as:
THD
(if available on the measuring device installed)
Harmonics
(if available on the installed measuring device)
Min, max, average values
(if available on the measuring device installed)
Status information
(if available on the device installed)
the storage time is limited according to:
total number of registered devices
number of "EQ" devices activated
type of registered devices (e.g. Energy meter, Multifunction
devices, ...)
Sampling of data (accuracy per minutes) is over time reduced, thus
passing to an accuracy per hour → per day → per month → per year
for the oldest stored data.
Technical data sheet: IDP000173EN_02
(continued)
PIN
PUK
00000 9999 00000
00000 8888 00000
00000 5555 00000
00000 1111 00000
(for more details refer to the user
.
Cat. N°: SXWS10/32
5. GENERAL CHARACTERISTICS
Real Time Clock:
. Internal RTCC circuit with back-up non-replaceable Lithium battery.
. Expected battery life without main power supply: ~3 years
. Expected battery life with main power supply: >10 years
Impulse withstand voltage:
. Aux. Supply:
wave 1,2 / 50 μs, 2 Ω: 0,5kV
. RS485 port:
wave 1,2 / 50 μs, 2 Ω : 0,5kV
wave 10/1000 μs : peak 600 W
Protection against electrostatic discharges:
. Port RS485, Terminals " + " and " - ":
human body model (HBM): 15 kV
discharge on contact with a metal object: 8 kV
Pollution degree
. 2
Ambient operating temperature:
. Min. = -0°C. Max. = +50°C
Ambient storage temperature:
. Min. = -20°C. Max. = +70°C
Plastic material:
. Self-extinguishing polycarbonate.
. Heat and fire resistant according to IEC/EN 60695-2-12, glow-wire
test at 960°C.
Protection Index:
. Protection index of terminals against direct contacts:
IP2X (IEC/EN 60529).
. Protection index of terminals against solid and liquid bodies (wired
device): IP 20 (IEC/EN 60529).
. Protection index of the front face against solid and liquid bodies: IP
40 (IEC/EN 60529).
. Class II, front panel with faceplate.
Consumption:
. 2,8 VA.
Average weight per device:
.
. 0,152 kg
Volume when packed:
.
. 0,685 dm
3
Consumption:
. 2,8 VA.
Updated: 14/02/2018
(continued)
:
Created: 10/10/2017
5 / 6