Nemo SX - Mini Energy Web Server
5. GENERAL CHARACTERISTICS
Case marking:
. By permanent ink pad printing:
Front face marking:
. Adhesive foil:
Lateral side marking:
. Adhesive foil:
Technical data sheet: IDP000173EN_02
Modbus RS485
bus wiring
terminals
Auxiliary supply
wiring terminals
RJ45 port for Ethernet
connection
Technical pictograms
Default IP address
Traceability information
Traceability information
and "Made in"
IME address
Serial number and
MAC address
Updated: 14/02/2018
Cat. N°: SXWS10/32
5. GENERAL CHARACTERISTICS
RS485 communication port's characteristics:
. Baud rate: 1200, 2400, 4800, 9600, 19200, 38400, 57600,
115200 bps
. Parity bit: none, even, odd
. Stop bit: 1 or 2
. Galvanically isolated respect to auxiliary supply
. Standard RS485 3 wires, half-duplex
. Protocol Modbus
RTU (not configurable)
®
. Default configuration:
baud rate: 19200 bps
parity bit: even
stop bit: 1
RS485 timeout: 300 ms
Signalling LEDs:
. Gives information about the operating state of the Web server:
. Front face
. Possible states & colours:
State
Led
Steady on
Device supplied
"Power"
(blue)
Off
Device not supplied
"RX"
Blinking
Receive data RS485 side
(red)
"TX"
Blinking
Transmission data RS485 side
(green)
. Lower part
. Possible states & colours:
Etat
Led
"Link"
Device connected to the Ethernet
Steady on
network
(yellow)
"Act"
Receive/Transmission data Ethernet
Blinking
side
(green)
Note: all LEDs and ports not described in this document do not have
any use in IME applications.
Created: 10/10/2017
(continued)
Meaning
Link
Act
Signification