DC Inverter Multi VRF System
7
8
9
10
11
12
Communication
13
parameters
14
Drainage system
15
Others
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Compressor
working current
Compressor's
IPM temp
IDU ambient
temp
Indoor heat
exchanger's inlet
temp
IDU
Indoor heat
parameters
exchanger's inlet
temp
Opening angle of
indoor EXV
Communication
data
——
——
GMV-H224WL/A-X
GMV-224WL/C-X
GMV-H280WL/A-X
GMV-280WL/C-X
GMV-H335WL/A-X
GMV-335WL/C-X
When ambient temperature is below 35℃, IPM
temperature is lower than 70℃. Maximum
temperature is 80℃.
——
●According to ambient temp, for a same IDU in
cool mode, the inlet temp will be 1℃~7℃ lower
than the outlet temp, and 4~9℃ higher than the
low pressure value.
●For a same IDU in heat mode, the inlet temp will
be 10℃~20℃ lower than the outlet temp.
●In cool mode, the opening angle of indoor EXV
varies within 40~480PLS.
PLS
●In heat mode, the opening angle of indoor EXV
varies within 70~480PLS.
Number of IDUs detected by software is the same
with the actual number. No communication error.
Indoor unit can drain water out completely and
smoothly. Condensate pipe has no backward
slope of water; Water of outdoor unit can be
drained completely through drainage pipe. No
water drop from unit base.
Compressor and indoor/outdoor fan motor do not
have strange noise. Unit can operate normally.
29
When compressor works
normally, the current is no
more than 18.0A.
When compressor works
normally, the current is no
more than 23.0A.
When compressor works
normally, the current is no
more than 25.0A.