1.4
Connection to the Gas Supply Line
NOTE: The gas supply (service) line must be the same size or
greater than the fryer inlet line. This appliance is equipped with
a ½-inch (15-mm) inlet. The gas supply line must be sized to
accommodate all gas-fired equipment connected to the line.
Consult the local gas company or supplier, or your local
contractor for minimum supply line requirements.
NOTE: If quick-disconnect supply lines or flex lines are used,
increase supply line size to ¾-inch (22-mm) or larger.
A manual shut-off valve must be installed in the gas supply (service) line upstream of this appliance and in
a position where it can be reached quickly in the event of an emergency.
The fryer must be connected to the gas supply specified on the rating and serial number plate located on
the inside of the appliance door. DO NOT ATTACH THIS APPLIANCE TO A GAS SUPPLY FOR WHICH IT IS
Before connecting new pipe to this appliance, the pipe must be blown out thoroughly to remove all foreign
material. Foreign material in the burner and gas valve will cause improper and potentially dangerous
All connections must be sealed with a joint compound suitable for the gas being used and all connections
must be tested for leaks using a solution of soapy water before lighting any pilots. Never use matches,
candles, or any other ignition source to check for leaks. If gas odors are detected, shut off the gas supply
to the appliance at the main shut-off valve and immediately contact the local gas company or an authorized
Adequate means must be provided to limit the movement of fryers without depending upon the gas line connections. If a
flexible gas hose is used, a restraining cable must be connected at all times when the fryer is in use. NOTE: The
installation must be inspected after it is complete to ensure it meets the intent of these instructions. The on-site
supervisor and/or operator(s) should be informed that the appliance is installed with restraints. If restraints are
removed to move fryer (cleaning beneath and behind, relocation, etc.), ensure that they are re-installed when
fryer is returned to its permanently installed position.
1.5 Gas Conversion Procedures
This appliance was configured at the factory for a specific type of gas. Converting from one gas type to
another requires the installation of specific gas-conversion components.
Switching to a different type of gas without installing the proper conversion components may result in fire
or explosion. NEVER ATTACH THIS APPLIANCE TO A GAS SUPPLY FOR WHICH IT IS NOT CONFIGURED!
Conversion of this appliance from one type of gas to another should only be performed by qualified,
licensed, and authorized installation or service personnel, as defined in Section 1.5 of this manual.
SUPER RUNNER SERIES GAS FRYERS
CHAPTER 1: INSTALLATION INSTRUCTIONS
NOT CONFIGURED!
operation.
service agency for service.
Propane Applications:
Propane Applications:
Proper Regulator Must Be
Proper Regulator Must Be Installed
DANGER
DANGER
DANGER
DANGER
DANGER
1-3
Installed
Regulator