LOCATION
The equipment area must be kept free and clear of combustible substances.
Installation clearances:
The installation location must allow adequate clearances for servicing and proper operation. A minimum
front clearance of 35" (889 mm) is required.
The ranges are suitable for installation on combustible floors when 6" (152 mm) adjustable legs or
casters are used. When legs or casters are removed, use only on noncombustible floors, curb, or
platform, with front appliance base projecting 3" (76 mm) beyond curb or platform.
The range(s) must be installed so that the flow of combustion and ventilation air will not be obstructed.
Adequate clearance for air openings into the combustion chamber(s) must be provided. Make sure
there is an adequate supply of air in the room to allow for combustion of the gas at the burners.
INSTALLATION CODES AND STANDARDS
Your Wolf Range must be installed in accordance with:
In the United States of America:
1. State and local codes.
2. National Fuel Gas Code, ANSI-Z223.1/NFPA #54 (latest edition). This shall include but
not be limited to: NFPA #54 Section 10.3.5.2 for Venting. Copies may be obtained
from The American Gas Association Accredited Standards Committee Z223, @ 400 N.
Capital St. NW, Washington, DC 20001 or the Secretary Standards Council, NFPA, 1
Batterymarch Park Quincy, MA 02169-7471.
NOTE: In the Commonwealth of Massachusetts
All gas appliances vented through a ventilation hood or exhaust system equipped with
a damper or with a power means of exhaust shall comply with 248 CMR.
3. NFPA Standard # 96 Vapor Removal from Cooking Equipment, latest edition, available
from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269.
In Canada:
1. Local codes.
2. CAN/CSA-B149.1 Natural Gas Installation (latest edition)
3. CAN/CSA-B149.2 Propane Installation Code (latest edition), available from the
Canadian Gas Association, 178 Rexdale Blvd., Etobicoke, Ontario, Canada M9W 1R3
The above are available from the Canadian Standard Association, 5060 Spectrum Way, Suite 100,
Mississauga, Ontario, Canada L4W 5N6.
COMBUSTIBLE
CONSTRUCTION
Back:
6" (152 mm)
Right Side:
10" (254 mm)
Left Side:
10" (254 mm)
- 4 -
NON-COMBUSTIBLE
CONSTRUCTION
0"
0"
0"