Combustion analysis

A fume sampling point has been included inside the boiler, in the top part of the anti-
backflow device (see fig. 6).
To take the sample:
1.
Remove the boiler top panel
2.
Remove the insulation placed over the anti-backflow device
3.
Open the fume sampling point;
4.
Insert the probe;
5.
Adjust the boiler temperature to max.
6.
Wait 10-15 minutes for the boiler to stabilise*
7.
Take the measurement.
fig. 6 - Combustion analysis
Analyses made with an unstabilised boiler can cause measurement errors.
A
Burner assembly removal and cleaning
To remove the burner assembly:
Disconnect the power and turn off the gas ahead of the boiler.
Remove the electronic flame controller "A" from the gas valve (fig. 7).
On models 97 2S and 107 2S with 2 gas valves, undo the 2 screws securing the 2
electrical connectors that feed the second valve and remove them from it (fig. 8).
Disconnect the ignition and ionisation cables from the electrode assembly.
Undo the nut "B" fixing the gas feed pipe ahead of the gas valve (fig. 7). On models
97 2S and 107 2S, undo the 2 nuts (fig. 8).
Undo the 2 nuts "C" fixing the combustion chamber door to the cast iron elements
of the boiler.
Remove the burner assembly and combustion chamber door.
Check and clean the burners. Only use a non-metallic brush or compressed air to clean
the burners and electrodes; never use chemical products.
On completion, refit everything in reverse order.
B
A
C
fig. 7 - Models PEGASUS - 67 2S, 77 2S and 87 2S
32
EN
PEGASUS 67 ÷ 107 2S
A
Pilot burner assembly
1.
Combustion chamber door
2.
Inspection door
3.
Pilot burner
4.
Ignition electrode
5.
Detection electrode
6.
Pilot nozzle
7.
High voltage cable
8.
Gas feed pipe
C
cod. 3540S434 - Rev. 00 - 10/2020