Installation and maintenance manual
5.1.1.2
The display
If the equipment is in the "ON" status, during
normal operation, the display will show the
established temperature by means of parameter
P5:
If P5 = 0, the display will show the temperature
of the upper part of the boiler;
If P5 = 1, the display will show the active
working set point;
If P5 = 2, the display will show the temperature
of the lower part of the boiler;
If P5 = 3, the display will show the temperature
of the evaporator;
If the equipment is in the "stand-by" status, the
display will be switched off.
5.1.1.3
Alarms
AL
Minimum temperature alarm
Solution:
- Check the temperature associated with the
alarm;
- Parameters displayed: A0, A1, A2 and A11.
Main consequences:
- The equipment will continue to work as
normal
AH
Maximum temperature alarm
Solutions:
- Check the temperature associated with the
alarm;
- Parameters displayed: A3, A4, A5 and A11.
Main consequences:
- The equipment will continue to work as
normal.
id
Digital input alarm
Solutions:
- Check the causes that originated the input
activation (possible short circuit in signal
cables)
- See parameters: i0; i1 and i2;
Main consequences:
- Compressor will be switched off;
- Defrosting will not be activated.
iSd
Blocked equipment alarm
Solutions:
- Check the causes that originated the digital
input activation
- See parameters: i0; i1; 18 and i9
- Switch the equipment off and then back on
again or disconnect the equipment from the
mains power supply.
Main consequences:
- Compressor will be switched off;
- Defrosting will be never activated.
FiL
Ventilation filter check alarm
Solutions:
- Check how clean the filter is (to switch off the
alarm message, press any key on the display)
UtL
Probable fan fault
Solutions:
- See parameters SP10 and C14
- Check the fan conditions
Main consequences:
- Compressor and fan are switched off;
- Water heating occurs using only the electric
resistance.
When the cause of the alarm has been
removed,
the
equipment is restored.
normal
operation
of
pag. 15 / 23
the