Technical Data
Type
Winding Resistances
Rotor
Stator, Main Winding per section
Stator, Auxiliary Winding
Rotor, Auxiliary Winding
Generator Protection
Main circuit
8
Type
Winding Resistances
Rotor
Main (stator) winding per section
Auxiliary Winding, stator
Auxiliary Winding, rotor
Generator Protection
Main circuit
N.B.:
All the above information is based on generator sets with a frequency of 50 Hz.
62
GHS4SI
GHS6.5SI
(BWG430)
(BWG830)
1,8 Ω
11,9 Ω
0,6 Ω
0,28 Ω
2,8 Ω
1,77 Ω
Automatic fuse (Circuit Breaker)
6 A
20 A
GHS14SI
GHS14TI
(BCI162G)
(BCI162E)
1,09 Ω
0,89 Ω
0,10 Ω
0,42 Ω
19 Ω
18 Ω
0,27 Ω
0,26 Ω
Automatic fuse (Circuit Breaker)
50 A
3 x 6 A
GHS8SI
GLS6.5SI
(BWG830)
(BWG615E)
11,9 Ω
1,15 Ω
0,28 Ω
0,45 Ω
1,77 Ω
20 Ω
0,21 Ω
25 A
20 A
GHS24SI
GHS24TI
(BCI182K)
(BCI162G)
1,4 Ω
1,09 Ω
0,095 Ω
0,21 Ω
20 Ω
19 Ω
0,21 Ω
0,27 Ω
80 A
3 x 32 A
GLS14SI
(BCI184E)
0,64 Ω
0,20 Ω
20 Ω
0,21 Ω
50 A
GLS14TI
GLS25TI
(BCI164D)
(BCI184F)
0,56 Ω
0,74 Ω
0,3 Ω
0,13 Ω
19 Ω
22 Ω
0,26 Ω
0,23 Ω
3 x 6 A
3 x 36 A