10 - JUMPER SW15
The settings are stored during the rest phase (gate closed).
The default settings are highlighted in the boxes with grey background.
JUMPER
Function
TERMINAL 23
SW15
FUNCTIONING
11 - TRIMMER ADJUSTMENT
Trimmer
Default
FORCE
RUN
TIME
P.S.
TIME
PAUSE
12 - FINAL CHECKS
Before powering the control unit, proceed with the following checks:
• Check the electrical connections; improper connection may be harmful to both the control unit and the operator.
• Check that the limit switches (if used) are in the correct position.
• Always provide for mechanical stops during opening and closing
• Adjust the RUN TIME trimmer setting the desired run time (up to maximum 103 seconds turning clockwise).
• Adjust the P.S. TIME trimmer setting the desired phase shift time.
• Adjust the PAUSE trimmer setting the desired pause time (up to maximum 103 seconds turning clockwise).
• Set the DIP switches for the desired operation.
Description
Status
N.C. devices are connected to STOP/COSTA input (23)
Resistive 8,2Ohm devices are connected to STOP/COSTA input (23)
Description
Turning clockwise adjusts (increases) the motor torque from 25% to 100%.
In the first 3 seconds, a pick-up with 100% power occurs.
Turning clockwise adjusts (increases) the run time from 2 to 103 seconds.
Turning clockwise adjusts (increases) the closing delay time of leaf 1 with respect to leaf 2
from 0 to 20 seconds. The phase shift during opening is fixed at 2 seconds.
Set to minimum, the delays during both opening and closing will be cancelled
(version with 2 sliding gates with consequent deactivation of the hammer stroke).
Turning clockwise adjusts (increases) the pause time from 3 to 103 seconds.
If adjusted to minimum, automatic closing is disabled only if STEP-BY-STEP WITH STOP
logic is set (DIP1_2 = OFF).