8.2.2.2 Installing the metering lock
NOTE
1 +3
+
4
= Input metering monitoring with electronic switch (NPN) with selection input „metering
lock" at configuration metering monitoring (see chapter 10.3.13).
PIN
Assignment
1
5 V, DC
3
Relay input
4
GND (┴)
8.2.3
Connector assignments of Slot VIII (5-terminal)
input for pulse, standard signal input and metering lock
Fig. 8.9
Connector assignments of Slot VIII (5-terminal), input for pulse, standard signal input and metering lock
Remove the protective cap
Mount the connector plug according to the connector assignment.
WARNING
8.2.3.1 Installing the pulse control (water meter)
Fig. 8.10 Installing the pulse control (water meter)
417101441_EMP_III_E60.docx
The metering lock function must be activated in menu first. The selection must also be
made of whether the pins
used for the metering monitoring input (see chapter 10.3.14).
Conductor coloring
Pin
(cable connection)
1
brown
2
white
3
blue
black
4
5
grey
Only use a connector plug from our product range!
2+4
(input "pulse") or
3+4
3
+
4
= Input metering monitoring with
potential-free contact, with selection
„metering lock" at configuration
metering monitoring
(see chapter 10.3.13).
PIN
Assignment
3
Relay input
4
GND (┴)
Fig. 8.8
Installing the metering lock
Assignment
Output 5 V, DC (load with max. 50 mA)
Input external pulse
Input metering lock
GND (┴)
Input standard signal 0/4-20 mA
2
+
4
= Pulse input with potential-free contact
PIN
Assignment
2
Relay input
4
GND (┴)
1
+
2
+
4
= Pulse input with electronic switch (NPN)
PIN
Assignment
1
5 V, DC
2
Relay input
4
GND (┴)
The minimum pulse- or pause time is 15 ms.