Connecting Electrical Loads
1. Make sure the green output indicator light comes on (it
may take up to three seconds).
2. Let engine stabilize and warm up for a few minutes
after starting.
3. Plug in and turn on the desired 120 Volt AC, single
phase, 60 Hz electrical loads.
NOTICE When plugging into the 120 Volt duplex
receptacles, plug items to be powered in sequence as shown
below.
1
3
NOTICE
• DO NOT connect 240 Volt loads to the 120 Volt
receptacles.
• DO NOT connect 3-phase loads to the generator.
• DO NOT connect 50 Hz loads to the generator.
• DO NOT OVERLOAD THE GENERATOR. See Don't
Overload Generator.
NOTICE Exceeding generators wattage/amperage capacity
could damage generator and/or electrical devices connected
to it.
• DO NOT exceed the generator's wattage/amperage capacity. See
Don't Overload Generator in the Operation section.
• Start generator and let engine stabilize before connecting
electrical loads.
• Connect electrical loads in OFF position, then turn ON for
operation.
• Turn electrical loads OFF and disconnect from generator before
stopping generator.
18
Parallel Operation
Two Briggs & Stratton P3000 inverter generators can be run
in parallel with a Briggs & Stratton parallel operation kit
(optional equipment) for a total output of power of up to
4,800 watts (4.8 kW).
NOTICE Total electrical load connected to the parallel kit
must not exceed 4,800 watts (4.8 kW).
See the parallel operation kits instruction sheet for detailed
instructions on installation and operation of the connected
generators.
NOTICE
2
4
• Turn electrical loads OFF and disconnect from both
generators.
• The POWERSMART switch must be in the same
position on both generators.
• Connect the power cables to both generators before
starting the engines. See instruction sheet supplied
with parallel kit.
• Start engine on one of the inverter generators
according to Starting the Engine in the Operation
section.
• Once the green LED output indicator light on the first
generators is steady, start second generator.
• Connect and turn on electrical loads to the parallel
panel receptacles.
• DO NOT disconnect power cables after engines have
been started.
• Shut down engines as described in Stopping the
Engine.
BRIGGSandSTRATTON.COM