OPTIONS DE DÉSHUMIDIFICATION DE LA CARTE DE COMMANDE DE L'ECM – SÉQUENCE D'OPÉRATIONS
DÉMARRAGE
G = ACTIVÉ
NON
OUI
CONTRÔLE DE COMMUTATEUR
DIP – ÉTAT DE RÉGLAGE/DÉLAI
RÉGL = NORMAL
NON
OUI
DÉLAI = A
NON
OUI
COMMUT.
HGRH = OUI
NON
OUI
J01-10 = 24 V c.a.
P13-H = TB01-H
Y1 = ACTIVÉ
NON
OUI
LA SOUFFLANTE
FONCTIONNE EN MODE
PI³/MIN PARTIEL –
POURCENTAGE Y1
NON
Y2 = ACTIVÉ
OUI
LA SOUFFLANTE
FONCTIONNE EN MODE
PI³/MIN MAXIMAL –
POURCENTAGE Y2
TB01-H
OUI
NON
18
LE MOTEUR
FONCTIONNE
AVEC TOUS LES
SIGNAUX
NON
OUI
RÉGL = +
RÉGL = -
NON
OUI
OUI
DÉLAI = B
DÉLAI = C
NON
OUI
OUI
IMPORTANT :
LORSQUE LE COMMUTA-
TEUR DIP EST RÉGLÉ À OUI,
LA LIGNE BK EST
TOUJOURS ALIMENTÉE,
AVEC OU SANS LE SIGNAL
TB1-H
SOUFFLANTE SEULEMENT,
PI³/MIN (KFAN)
W1 OU W2 =
ACTIVÉ
NON
OUI
PI³/MIN NOMINAL DE
LA SOUFFLANTE
COMMANDE LE MOTEUR EN
MODE PI³/MIN NOMINAL
ALIMENTE LA SORTIE H
P13-H = ACTIVÉ
Fig. 16 - Séquence de fonctionnement de l'ECM
Les spécifications peuvent changer sans avis préalable.
IMPORTANT :
LES RÉGLAGES ADJ + ET ADJ -
RÉGL = TEST
AUGMENTENT OU DIMINUENT LA
NON
NON
VALEUR EN PI³/MIN NOMINALE
D'ENVIRON 15 % SÉLECTIONNER LE
PROFIL DE PI³/MIN, DÉLAIS A,B,C OU
D (DÉLAIS PAR DÉFAUT = A)
OUI
DÉLAI = D
NON
NON
OUI
REFROIDISSEMENT POUR DÉSHUMIDIFICATION
P13-H = 0
TB01-H = ACTIVÉ
NON
ACTIVE LA DÉSHUMIDIFICA-
TION DU CIRCUIT DU MOTEUR –
DÉSACTIVE J01-10 (BK10 = 0)
LORSQUE LE SIGNAL H DU
THERMOSTAT EST DÉTECTÉ
Y1 = ACTIVÉ
OUI
LA SOUFFLANTE
FONCTIONNE EN MODE
PI³/MIN PARTIEL –
POURCENTAGE Y1 – RÈGLE
LE TEMPS DE
DÉSHUMIDIFICATION
Y2 = ACTIVÉ
OUI
LA SOUFFLANTE
FONCTIONNE EN MODE
PI³/MIN PARTIEL –
POURCENTAGE Y2 – RÈGLE
LE TEMPS DE
DÉSHUMIDIFICATION
MOTEUR DE
SOUFFLANTE =
DÉSACTIVÉ
OUI
IMPORTANT :
LORSQUE LE COMMUTATEUR DIP
EST RÉGLÉ À NON, LA LIGNE BK
EST TOUJOURS ALIMENTÉE. ELLE
N'EST PAS ALIMENTÉE
SEULEMENT LORSQUE LE SIGNAL
TB01-H 24 V c.a. EST DÉTECTÉ
NON
NON
228 01 1100 01FR