COMBUSTION ADJUSTMENT
In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment
and testing must be carried out observing the instruction manual of the boiler, including verification of
the CO and CO
concentration in the flue gases, their temperatures and the average temperature of
2
the water in the boiler.
To suit the required appliance output, choose the proper nozzle and adjust the pump pressure, the
setting of the combustion head, and the air damper opening in accordance with the following schedule.
The values shown in the table are measured on a CEN boiler (as per EN 303).
They refer to 12.5% CO
Nozzle
1
GPH
Angle
60°
0.65
60°
0.75
60°
0.85
60°
1.00
60°
1.10
60°
1.25
1
NOZZLES RECOMMENDED : Monarch type R - NS;
2
PUMP PRESSURE:
3
COMBUSTION HEAD SETTING
This is done when fitting the nozzle, with the blast tube removed. It depends on the output of the
burner and is carried out by rotating the regulating rod, till the terminal plane of the blast tube is level
with the set-point, as indicated in the schedule.
Terminal plane of the blast tube
5
D5402
Blast tube
2393
at sea level and with light oil and room temperature of 20 °C.
2
Pump
pressure
2
bar
12
12
12
12
12
12
Steinen
12 bar - The pump leaves the factory set at this value.
14 bar - Improves flame-retention; it is therefore suitable for ignitions
at low temperatures.
2
3
1
Regulating rod
Shutter
Comb. head
Burner
adjustment
output
kg/h ± 4%
Set-point
2.6
3.0
3.4
4.0
4.4
5.0
Delavan type W - A - E
type Q - H ;
Danfoss type B - H
In the sketch on the left below, the
combustion head is set for an output
of 0.85 GPH at 12 bar, while the
shutter is level with set-point 3.5, as
required by the above table.
6
GB
Air damper
adjustment
3
4
Set-point
2
2.2
2.5
2.5
3.5
3
4.5
4
5.5
5
6
6