Service
CAUTION!
This piece of equipment uses a R290 Refrigeration system. This equipment has been
COMPONENT PARTS SHALL BE REPLACED
clearly marked on the serial tag the type of refrigerant that is being used. There is also a
WITH LIKE COMPONENTS. SERVICE WORK
warning labels stating that the unit contains R290 refrigerant.
SHALL BE DONE BY FACTORY AUTHORIZED
SERVICE PERSONNEL, SO AS TO MINIMIZE
No smoking or open flames when servicing this equipment. If needed, use a CO
or
2
THE RISK OF POSSIBLE IGNITION DUE TO
dry=power type fire extinguisher
INCORRECT PARTS OR IMPROPER SERVICE.
Only authorized service technician, certified in R290 system should service this equipment.
MANIFOLD SET
A R134A manifold set can be used for servicing this equipment.
REFRIGERANT RECOVERY
Follow all national and local regulations for R-290 refrigerant recovery.
LEAKING CHECKING AND REPAIR
Leak check an R-290 system the same way you would an R-134a or R-404A system with
the following exceptions.
1. Do not use a Halid leak detector on a R290 system.
2. Electronic leak detector must be designated specifically for combustible gas.
Use of a bubble solution or an ultrasonic leak detector are acceptable.
When repairing a leak, it is recommended using oxygen free dry nitrogen with a trace gas
not exceeding 200PSI.
When accessing an R290 system, piercing valves are not to remain on the equipment in
a permanent manner. After charge is recovered, Schrader valves are to be installed on the
process stubs. Proper charge is to be weighed into the system and the system is to be
leak checked afterwards.
The R290 equipment must have red process tubes and other devices through which the
refrigerant is serviced, such as any service port. This color marking must remain on the
equipment. If marking is removed, it must be replace and extend at least 2.5 centimeters
(1") from the compressor.
CHARGING
Follow the charge amount specified on the data tag. It is recommended to use the shortest
hoses possible to prevent undercharging.
• Ensure the system is sealed and leak checked
• Evacuate system to a minimum 500 micron
• Weigh in correct charge
• Leak check the system again
• Bleed the refrigerant from the high side hose to the low side hose
• Disconnect the hoses
• Remove line taps