Automatic offset correction:
Contact
pin side
Plug for
display
select
up down
ON
1 2 3 4 5 6
DIP switches
1 2 3 4
1. The device must be operative for at least 60 minutes before zero
point setting is started.
2. Connect pressure connections P (+) and P (–) with a hose
(differential pressure between the connections = 0 Pa).
3. Requirement: DIP-switch 6 is set to OFF.
4. To set the zero point, press pushbutton for 10 seconds without
interruption.
By pressing the button, a countdown of ca. 10 seconds is started.
The yellow LED is flashing and the countdown counter is shown on the
display (optional).
After the countdown period has elapsed, zero point calibration takes
place. This is indicated by continuous light of the LED, and on the
display (optional) by switching from "AUTO 0" to "PROG 0".
Note: When releasing the pushbutton during countdown (counter > 0),
zero point setting is immediately aborted !
Setup button assignment:
select
Pressing for more than 5 seconds =>
switches to setup mode
A short push following thereafter =>
switches to the next input value
respectively terminates setup mode
up ▲
(arrow pointing up) increases the input value. Keeping it
depressed increases the increment step by step by
which the parameter is increased.
down ▼
(arrow pointing down) decreases the input value.
Pressing for longer increases the increment step by
step by which the parameter is decreased.
Calculation formula – k-factor:
k = q ⁄
(Pi)
q = volume flow rate in m
(Pi) = differential pressure in Pa
Adjustment range: 1...3000
Plug for display
min. max.
Offset correction
see graph
ca. ± 10%
Offset
Offset
Pushbutton
Zero point settin
auto
auto
zero
zero
DIP
LED
3
⁄ h
Volume flow rate indication on the display:
1160 / PREMASREG
PREMASGARD
®
1
st
line showing volume flow rate value
2
nd
line showing corresponding measurement unit
®
At the PREMASREG
1161 in addition, the switching
status of the relay is indicated in the second line :
Circle empty = relay in idle state
Circle solid
= relay activated
At putting in operation, DIP switch 5 enables switching
over to displaying pressure values.
Pressure reading at the display:
1
st
line showing actual pressure up to the measuring range limit.
Pa = Pascal
Precondition: DIP switch 5 is set to ON.
Setup mode
Input k-value: 1...3000
1
st
line showing set value
2
nd
line showing type, flashing at a one-second cycle
Input measurement unit:
(Displayed unit of volume flow rate)
3
3
0 = m
⁄ s, 1 = m
⁄ min, 2 = m
Input volume flow rate at max. output signal 10 V:
Setting (measuring range end value ^ = 10 V)
10% to 100% of max. possible volume flow rate
in the selected measurement unit.
Input relay switching threshold at volume flow rate:
Setting (relay switchpoint)
10% to 100% of max. possible volume flow rate
in the selected measurement unit.
14
®
1160
3
⁄ h, 3 = liters ⁄ s, 4=liters ⁄ min, 5 = liters ⁄ h