S+S Regeltechnik PREMASGARD 1160 Notice D'installation page 12

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Schematic diagram
Contact
pin side
Plug
display
select
up down
ON
1 2 3 4 5 6
DIP switches
1 2 3 4
DIP switches for
volume flow or pressure, output attenuation and zero compensation:
Output attenuation
Time span
selectable
great (10 s)
slight (1 s)
Usually a Wilson flow grid is used to for detection of the airflow, or the applied ventilator has corresponding pressure connections for
the indication of the volume flow. Here the airflow is represented by a differential pressure. The K-factor specified for the products is used
for the adjustment of the volume flow measuring transducers. When different measuring probes or arrangements are applied, the K-factor
must be determined by way of the parameters on which the air duct geometry or measurement systematics is based.
PREMASGARD
Plug for display
min. max.
Offset correction
see graph
ca. ± 10%
Offset
Offset
Pushbutton
Zero point setting
auto
auto
zero
zero
DIP
LED
DIP switches 1, 2 and 3
are not assigned!
Volume flow rate ⁄ pressure
Display readout
DIP 4
selectable
OFF
Volume flow rate
O N
Pressure (service)
®
1160
Schematic diagram
with Display
Zero point calibration
Function
DIP 5
selectable
OFF
Pushbutton (auto zero)
O N
Potentiometer (Offset)
12
min.max.
Plug
display
Offset
select
auto
up down
zero
ON
DIP
LED
1 2 3 4 5 6
DIP switches
12 11 13
1
2 3 4
NC NO
DIP 6
OFF
O N
PREMASREG
®
1160
with Display
Plug for display
Offset correction
see graph
ca. ± 10%
Offset
Pushbutton
Zero point setting
auto
zero
DIP switches 1, 2 and 3
are not assigned!
ON
DIP
1 2 3 4 5 6