LC 05
LC 03
LC 02
LC 01
LH 00
LC 06
LH 07
NA
FOR EACH ERROR:
Switch off the unit and wait 2 minutes before restarting it, if the problem persists, please contact the
assistance centre.

5.2 - OTHER ERROR

The display board may show a garbled code or a code undefined by the service manual. Ensure that this
code is not a temperature reading.
test the unit using the remote control.
- if the unit does not respond to the remote, the indoor PCB requires replacement.
- if the unit responds, the display board requires replacement.
frequency limit caused by voltage
frequency limit caused by current
frequency limit caused by tP
frequency limit caused by t3
frequency limit caused by t2
frequency limit caused by PfC
frequency limit caused by remote controller
no malfunction or pretecion