Class 7 Status Codes - Fronius Galvo 1.5-1 208 Instructions De Service

Masquer les pouces Voir aussi pour Galvo 1.5-1 208:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Code
Description
Function incompatibility (one
or more PC boards in the in-
558
verter are not compatible with
each other, e.g., after PC
board replacement)
Power derating due to over-fre-
560
quency
566
Arc detector switched off
(e.g., with external arc moni-
toring)
Class 7 Status
Class 7 status codes concern the inverter control unit, configuration and data recording,
Codes
and can directly or indirectly affect grid feed operation.
Code
Description
Conflict between inverter num-
705
bers (e.g., number is assigned
twice)
EEPROM was reinitialized or
721
EEPROM is defective
Initialization error – USB stick
731
is not supported
732
Overcurrent on the USB stick
733
No USB stick inserted
Update file is not detected or is
734
not available
Update file does not corre-
735
spond to the device, update file
is too old
Details
Possible error displays or mal-
functions in the inverter.
The status code is displayed
with excessive grid frequency.
The inverter reduces the pow-
er.
The status indicator is dis-
played until the inverter re-
sumes normal operation.
The status code is displayed
every day until the arc detector
is activated again.
Details
-
Warning message is shown on
the display.
Warning message is shown on
the display.
Warning message is shown on
the display.
Warning message is shown on
the display.
Warning message is shown on
the display; update process is
canceled.
Rectification
If this status code keeps recur-
ring, contact your system in-
staller.
As soon as the grid frequency
returns to the permissible
range and the inverter re-
sumes normal operation, the
error is rectified automatically.
If the status code persists,
contact your system installer.
No error!
Confirm status code displayed
by pressing the "Enter" key.
Rectification
Correct inverter number in Set-
up menu
Acknowledge status code.
If status code persists: contact
a Fronius-trained service tech-
nician.
Check or replace the USB
stick.
Check the USB stick file sys-
tem.
If status code persists: contact
a Fronius-trained service tech-
nician.
Insert or check the USB stick.
If status code persists: contact
a Fronius-trained service tech-
nician.
Check the update file (e.g., for
the proper file name).
If status code persists: contact
a Fronius-trained service tech-
nician.
Check the update file.
If necessary, download the
correct update file for the de-
vice (e.g., at http://www.fro-
nius.com).
If status code persists: contact
a Fronius-trained service tech-
nician.