the proper ventilation and are not suitable for use with the
cooktop.
Select Hood and Blower Models:
•
For wall installations the hood width must, at a
minimum, equal the nominal width of the appliance
cooking surface. Where space permits, a hood larger in
width than the cooking surface may be desirable for
improved ventilation performance.
•
For island installations the hood width should, at a
minimum, overhang the appliance cooking surface by
3" on each side.
Hood Placement:
•
For best smoke elimination, the lower edge of the hood
should be installed 30" above the appliance cooking
surface. (See Figure 1).
•
If the hood contains any combustible materials (i.e., a
wood covering), it must be 36"or greater distance
above the cooking surface.
Cooktop
Width
Configuration
24"
24" griddle -or-24" wok
30"
4 burners
4 burners w/ grill -or-
griddle
36"
6 burners
4 burners w/ grill-griddle
combo
24" griddle or wok
48"
6 burners w/ grill -or-
griddle
Important Notes:
•
It is recommended that a Thermador Professional wall or island hood or custom insert is used with Thermador
Professional Cooktops.
•
Refer to www.Thermador.com for a complete selection of Professional Ventilation options, Blowers, and
Accessories.
•
* For high output gas cooktops (60,000 BTU or greater), the minimum of one (1) CFM of ventilation per 100 BTU is
recommended. If the cooktop has a grill or griddle, add 200 CFM to the estimated blower capacity. Add 400 CFM if
the cooktop has a 24" griddle or wok. Additional blower capacity may be required for longer duct runs.
•
For island applications, it is recommended to use a hood width that exceeds the width of the cooktop by 6"
(overlapping the cooktop by 3" on each end).
•
CFM = "cubic feet per minute" (standard blower capacity rating).
English 4
Cooktop
Minimum Recommended
Blower Capacity*
NOTICE:
Most hoods contain combustible components which must
be considered when planning the installation.
Consider Make-Up Air:
•
Due to the high volume of ventilation air, a source of
outside replacement air is recommended. This is
particularly important for tightly sealed and insulated
homes.
•
A qualified heating and ventilating contractor should be
consulted.
NOTE:
Ventilation hoods and blowers are designed for use with
single-wall ducting. Some local building codes may require
double-wall ducting. Before starting installation, consult
local building codes and agencies to insure that the
installation will meet local requirements.
30" Pro Wall Hood
600 CFM
30" Custom Insert w/ optional blower
42" Island Hood w/ optional blower
30" or 36" Pro Wall Hood
600 CFM
30" or 36" Custom Insert w/ optional blower
42" Island Hood w/ optional blower
36" or 42" Pro Wall Hood
800 CFM
36" Custom Insert w/ optional blower
900 CFM
42" or 48" Island Hood w/ optional blower
48" or 54" Pro Wall Hood
1000 CFM
48" Custom Insert w/ optional blower
54" Island Hood w/ optional blower
1100 CFM
Ventilation Options