HOW TO INSTALL AN EARTH GROUND SYSTEM
Improperly earthed energizers can cause barns, gates etc to become hot. Follow
earthing instruc ons carefully.
The most eff ec ve place for an earth system is in con nuously damp soil (illustra on
a).
a)
Earth Clamp (G8760)
For dry areas with poor earthing condi ons, install the fence using illustra on b.
b)
Earth Clamp (G8760)
Earth stakes, at least 2m (6 ) long, should be spaced 3m (10 ) apart. Use a minimum
of 3 earth stakes for the M150, M300, M500.
HANDY HINT
Use Cut-out Switches (G6076) to allow sec ons of the fence
system to be switched off during fence maintenance. Put a
switch at each gateway and at every major change in fence
direc on.
10
All live wire system
(for areas with good earthing systems)
Green
Earth Stake (G8790)
An earth wire return system
(for areas with poor earthing)
Green
Earth Stake (G8790)
Gallagher 3E0682 Mains Energizer User Manual
The animal must touch the wire
and the ground to feel a shock
Red
The animal must touch both a live wire and
the earth wire to feel an eff ec ve shock
Red
Live
Live
Live
Live
Earth
Live