Positioning the heater - recess installation
To position the sauna heater in a recess:
1. Position the heater at a safe distance from the floor, side walls
and interior fittings (see Figure 5, Page 3).
2. Position the sensor according to the diagram (see Figure 5,
Page 3).
3
2
1
1
Figure 5: Positioning the heater - recess installation
1.
Minimum distance from side wall: 200 mm
2.
Sensor position: 200 mm from heater
3.
Sensor
4.
Max. 1000 mm
5.
Sensor position: 40 mm from ceiling, regardless of ceiling
height
6.
Minimum distance from ceiling: 1030 mm
7.
Minimum distance from interior fittings: 100 mm
8.
Minimum ceiling height: 1900 mm
9.
Minimum distance: 20 mm
10.
Minimum distance from interior fittings: 30 mm
11.
Distance from floor: 100-270 mm (with legs: 100 mm)
Positioning the inlet vent
Install the inlet vent straight through the wall under the centreline
of the heater. Vent size for a family sauna approx. 125 cm².
The air circulation from the door must concord with the hot air cir-
culation from the heater.
5
6
7
4
8
10
9
11
1
3
Figure 6: Positioning the inlet and outlet vents
1.
Inlet vent position.
2.
Outlet vent position through the sauna wall.
3.
Outlet vent position through the cavity.
4.
Outlet vent position via duct.
Positioning the outlet vent
DANGER! The outlet vent must not lead outdoors.
!
This could cause the ventilation direction to be re-
versed, which may negatively affect the heater tem-
perature cut-out.
DANGER! Any gap above the sauna ceiling should
!
not be sealed without leaving at least one vent hole
on the same wall as the sauna door.
Position the outlet vent
at the maximum possible distance from the inlet vent, e.g. di-
agonally (see Figure 6, Page 3).
high on the wall or in the ceiling (see Figure 6, Page 3).
so that it vents into the space the door and inlet vent open in-
to.
The outlet vent must have the same area as the inlet vent.
Ensure that the outlet vent is open.
Mechanical ventilation is not recommended due to the risk of poor
air exchange, which can negatively affect the heater temperature
cut-out.