Mechanical installation
Wall mounting
Wiring on the motor side
{
Danger!
All control terminals only have basic insulation (single isolating distance)
ƒ
after connecting a PTC thermistor or a thermal contact.
Protection against accidental contact in case of a defective isolating
ƒ
distance is only guaranteed through external measures, e. g. double
insulation.
X2
T1 T2
PE W V U
0.5...0.6 Nm
4.4...5.3 lb-in
3.4 Nm
30 lb-in
8200mot006
Use low−capacitance motor cable! (core/core £ 75 pF/m, core/shield £ 150 pF/m)
0
A motor cable that is as short as possible has a positive effect on the drive behaviour!
Cable cross−sections U, V, W, PE:
E82MV551_4B, E82MV751_4B
E82MV222_4B, E82MV152_4B
1
Install a separate cable (shielded) to X2/T1 and X2/T2 for the motor temperature monitoring.
Install control cables and mains cables with a spatial separation from the motor cable!
94
X2
T1 T2
T1
J >
X2
Fig. 4−2
1a
1a
®
1 mm
®
1.5 mm
l
PE
W V U
T2
PE
1a
B
A
2
(AWG 18), shielded
2
(AWG 16), shielded
0.5...0.6 Nm
4.4...5.3 lb-in
5.5 mm
2
2.5 mm
AWG 12
6mm
3.4 Nm
30 lb-in
EDK82MV222 DE/EN/FR 11.0