Code
Level
Variable Name
Nr.
110
Inst.
HUMIDITY LIMIT
111
Inst.
ANTIFROST T°
112
Inst.
HEAT CLIMATIC NUMBER
113
Inst.
REGION T° O
114
Inst.
STOP H T° O
115
Inst.
NO HEAT T W1
116
Inst.
MAX W T° W1
117
Inst.
NO HEAT T W2
118
Inst.
MAX W T° W2
119
Inst.
COOL CLIMATIC NUMBER
120
Inst.
MAX REGION T°
121
Inst.
COOL STOP T°
122
Inst.
MIN COOL W T°
123
Inst.
MAX COOL W T°
124
Inst.
MIN COOL W T°
125
Inst.
MAX COOL W T°
126
Inst.
AUX NUMBER
127
Inst.
BACKUP ELECBOIL
128
Inst.
EH PRIORITY
129
Inst.
AUX T° O
130
Inst.
AUX HYST
131
Inst.
AUX DELAY
132
Inst.
OAT BOILER
This code defines the Humidity threshold limit to enable the output for the external
de-humidifier.
This code defines the Temperature below which the water frost protection will be activated.
Climatic Curve
Use Days button to select Heat climatic curve:
0. - zone 1
0. No predefined climatic curve (Installer has to set the climatic curve)
1 - 6. See manual for climatic curve details
1. - zone 2
0. No predefined climatic curve (Installer has to set the climatic curve)
1 - 6. See manual for climatic curve details
Minimum outdoor T° depending on the country where the system is installed
(Heat Climatic Curve Zone 1 and 2)
If outdoor T° is equal to or greater than the value of this code, minimum water tempreature
is considered (Heat Climatic Curve Zone 1 and 2)
In Heat mode, minimum water T° going to terminal zone 1 (Heat Climatic Curve Zone 1)
In Heat mode, maximum water T° in terminal zone 1 (Heat Climatic Curve Zone 1)
In Heat mode, minimum water T° going to terminal zone 2 (Heat Climatic Curve Zone 2)
In Heat mode, maximum water T° in terminal zone 2 (Heat Climatic Curve Zone 2)
Use Days button to select Cool climatic curve:
0. - zone 1
0. No predefined climatic curve (Installer has to draw climatic curve)
1 - 2. See manual for climatic curve details
1. - zone 2
0. No predefined climatic curve (Installer has to draw climatic curve)
1 - 2. See manual for climatic curve details
Maximum outdoor T° depending on the Country where the system is installed
(Cool climatic curve zone 1 and 2)
If outdoor T° is equal to or less than the value of this code, maximum water tempreature is
considered (Cool climatic curve zone 1 and 2)
In Cool mode, minimum water T° going to terminal zone 1 (Cool climatic curve zone 1)
In Cool mode, maximum water T° going to terminal zone 1 (Cool climatic curve zone 1)
In Cool mode, minimum water T° going to terminal zone 2 (Cool climatic curve zone 2)
In Cool mode, maximum water T° going to terminal zone 2 (Cool climatic curve zone 2)
Backup heaters
Number of backup heaters
0. No backup heaters
1. 1 backup heater output (to be selected in case of boiler backup)
2. 2 backup heaters output (2
backup heater output activated after the 1
nd
output)
Defines the backup energy source:
1: Electrical heater
2: Gas boiler
This code defines the electric heater output priority between back-up heaters (space
heating) and booster heater (domestic hot water). It is only active if code 127 = 1
0. All the electric heaters output can be activated at the same time, if required
1. Maximum 2 electric heaters output can be activated; booster heater has the lowest
priority
2. Maximum 1 electric heater output can be activated; back-up heater output 1 has the
highest priority (backup heater output 2 is never ON)
3. Maximum 2 electric heaters output can be activated; booster heater has the lowest
priority (backup heater output 2 is never ON)
4. Maximum 1 electric heater output can be activated; booster heater has the highest
priority (backup heater output 2 is never ON)
The outdoor T° must be below this value to allow the backup heaters to be ON (unless there
is a failure to stop the outdoor unit and code 1.4 = 1)
If the difference between water setpoint and water temperature is higher than this value,
backup heaters are allowed to turn on
Time delay (minutes) before switching the backup heaters ON
If in Heat mode, the outdoor temperature is less than the value of this code, the outdoor unit
is turned OFF and the Boiler is used as heat source. Set to minimum value if this function is
not required.
DESCRIPTION
st
VALUE RANGE
DEFAULT
Min
Max
20
100
4 °C
10
0
6
-20 °C 10 °C
15 °C
50 °C
20 °C
60 °C
20 °C
80 °C
20 °C
60 °C
20 °C
80 °C
0
2
30 °C
50 °C
0 °C
25 °C
4 °C
20 °C
4 °C
20 °C
4 °C
20 °C
4 °C
20 °C
0
2
backup heater
80AW--
1
2
Others: 1
0
4
-30 °C +40 °C
0 °C
10 °C
0
60
-30 °C +40 °C
100
4 °C
0
-7 °C
20 °C
20 °C
35 °C
40 °C
55 °C
0
40 °C
22 °C
12 °C
18 °C
6 °C
12 °C
0
-M0: 2
0
+4 °C
3 °C
10
-5 °C
21