5.- Programming of the automatic mechanism:
5.1.- Recording the door run.
- Place the door in the closed position, either manually or using the push-buttons on the panel.
- Turn DIP 7 and DIP 8 to ON (Gentle stop options and encoder activated).
- Turn DIP 1 to ON (Check the ignition of the DL3 led).
- Turn DIP 2 to ON.
- Push Operation (Push-button E). The door begins to open.
- When the end run magnet is some 50 cm from the end of its run, press again so that the speed begins to
diminish.
- Press E for the door to begin to close.
- When the end run magnet is some 50 cm from the end of its run, press again so that the speed begins to
diminish.
- Turn DIP 1 to OFF.
- Turn DIP 2 to OFF.
5.2.- Recording partial opening (for pedestrians):
To carry out this recording we will connect a push-button normally open between the 2-COMMON and 3-ST2 terminals (Start 2).
- Turn the DIP 1 to ON.
- Turn the DIP 3 to ON.
- Press Peatonal. The door begins to open.
- Press Peatonal in the position in which we want the decrease to start.
- Press Peatonal to stop the door in the desired position of opening for pedestrians.
- Press Peatonal. The door begins to close.
- Press Peatonal in the position in which we want the decrease to start. The door will stop at the end of the run.
- Turn DIP 1 to OFF.
- Turn DIP 3 to OFF.
Note for all types of operation:
• If during the opening manoeuvre the door encounters an obstacle in its run, it will stop and close
for 2 seconds.
• If during the opening manoeuvre the door encounters an obstacle in its run, it will stop and invert
its movement until it stops in the open position.
• Whenever the door receives a key impulse or photocell in the opening manoeuvre, it will stop
and move to the open door position.
6.- Selection of operating mode.
6.1.- Automatic/Semi-automatic cycle:
Automatic Cycle (DIP 4 ON).
"Start" (Operation button) – Opening – Wait with door open (time can be regulated with timer G) – Closure.
If "operation" is pressed or any photocell is activated during the waiting time, the period will restart.
Semi-Automatic Cycle (DIP 4 OFF).
"Start" – Opening – "Start" – Closure.
21