FIRST START-UP,

Once you have made sure wiring is correct, and checked hydraulic connections
for leaks, set the air pressure switch to the minimum value.
Connect the pressure gauge to the gas pressure test point at the burner head
(M3, fig. 7 page 7).
The following table gives start-up settings with reference to a burner fuelled
with methane gas.
Reference values are:
– firing power;
– air damper preset position (CAM III);
– preset position of gas train POINT 0 setting screw;
– the model of gas train to be used.
Firing power
TYPE
kW
916M
26
33
917M
48
83
918M
68
110
917M
48
83
918M
68
110
Set to values close to start of scale (-1.5).
1 - Depending on required maximum output, adjust the combustion head as indicated on page 10.
2 - Select manual operating mode "MAN" and calibrate the servomotor's CAM III and adjust the 0 POINT
setting screw as indicated in the table, then start the burner.
3 - Once it has fired, move the servomotor by hand towards the second flame position by pressing switch
(+). During this operation, check flame stability: if it looks unstable, adjust the GAS/AIR RATIO setting
screw to increase or decrease the setting until you reach the maximum desired output and correct
CO
values for fumes. Next, set CAM I to the value reached by the servomotor.
2
4 - Move the servomotor by hand towards the first flame position by pressing switch (-).
Check combustion and, where necessary, use the 0 POINT setting screw only to achieve correct CO
values for fumes.
5 - If first flame output needs altering, adjust CAM III.
All 0 POINT setting screw adjustments will also cause the maximum gas delivery to be varied.
6 - Return the servomotor to maximum opening and check maximum output again, adjusting with the GAS/
AIR RATIO setting screw.
7 - Turn the servomotor to first flame position again and adjust output again, adjusting with the 0 POINT
setting screw only.
8 - Repeat steps (6) and (7) until GAS/AIR RATIO and 0 POINT setting screws no longer need adjusting.
9 - Check combustion values at intermediate output and, where necessary, adjust further with GAS/AIR
RATIO and 0 POINT setting screws.
Once you have done, and have made sure the burner features good firing and good flame stability, se-
lect automatic mode by setting the selector to "AUT". modulation will occur between the setting posi-
tion of CAM III and that of CAM I.
3134
(see fig. 13 and fig. 5 page 6)
Adjustment
Adjustment
CAM III
0 POINT
Set point
Set point
20°
30°
30°
40°
30°
35°
30°
40°
0.1
30°
35°
-0.7
Adjustment
GAS/AIR RATIO
Set point
Depends on maximum
output
0.25
Depends on maximum
output
-0.5