Notes on documentation, Safety instructions, Product description
1
Notes on documentation
This installation and short users guide is intended for experienced, trained specialists and contains
EN
only the most important information on the assembly, installation and function of the power distribu-
tion unit PDU international (subsequently called PDU).
1.1
Associated documents
Assembly, installation and users guide for the power distribution unit PDU international.
It is available at www.rittal.com and contains the complete application-related information and tech-
nical data on the PDU with regard to:
– Details of the electrical connection
– Functions and services
– Configuration options
– Detailed operating instructions
– Troubleshooting
2
Safety instructions
– The unit may only be assembled and installed by appropriately skilled personnel.
– Opening the PDU's housing is not allowed.
– The PDU must not come into contact with water, aggressive or inflammable gases or vapours.
– The PDU must only be operated within the specified ambient conditions (see section 3.3).
3
Product description
3.1
Functional description
The PDU is a power distribution unit for usage in IT racks. There are four design variants:
– PDU basic: compact basic powder distribution unit for the IT environment
– PDU metered: energy measurement per phase, i. e. power requirement of an entire IT rack
– PDU switched: measuring function per phase as well as individually switched outlet sockets
– PDU managed: high-end IT rack, power distribution with energy measuring and monitoring func-
tions for each individual outlet socket
A web server for a direct network connection with comprehensive user administration is integrated
into the PDU (not on PDU basic/slave PDU). The slave PDUs can be connected via a CAN bus in-
terface (not on PDU basic).
3.2
Proper use
The PDU is intended to be used in particular for the distribution of power in IT racks.
3.3
Operating conditions
The PDU is only allowed to be used under the following operating conditions:
Temperature application range:
Humidity application range:
Protection category:
7
+0 °C to +45 °C
10 % to 95 % relative humidity, non-condensing
IP20 to EN 60 529
Rittal Power distribution unit PDU international