Installation Instructions – WPMLED Wall Pack (B-Series)
INSTALLATION
Tools required:
Phillips head screwdriver, 1/4" Drill Bit.
1.
Open the fixture by loosening the two Phillips head
screws on the side opposite the hinges. Disconnect the
male and female connectors. Remove the glass door
assembly, and gently set it aside. (Figure 1)
2.
Align and drill mounting hole locations and secure back
housing to junction box or wall (mounting hardware not
supplied).
N
ote:
Mounting height to be a minimum of 6 feet.
3.
If using electrical conduit, remove the screw cap from
the desired conduit hole and replace with conduit,
sealing the conduit hole afterwards. Route the branch
circuit wires inside the fixture. If using a junction box,
bring the branch circuit wires through the rear hole into
the fixture.
4.
Splice the branch circuit power leads to the fixture
power leads, black to black (hot), white to white
(neutral), and green to green (ground).
5.
Make adjustments as necessary to Selctable CCT,
Lumen, and Photocontrol switches (if supplied, see
next sections for details).
6.
Replace the door assembly back on the hinges.
Reconnect the male and female connectors. Close and
secure the door assembly with the two Phillips head
screws.
IMPORTANT
To weatherproof your outdoor installation, use silicone
sealant for all holes in the fixture housing (mounting,
conduit, plugs, photocontrols, etc.) and all edges between
the fixture housing and the mounting surface. If you remove
one of the conduits plugs and use an alternate conduit
location, add thread sealing tape to plug and tighten to
15 in-lbs to ensure watertight seal.
SELECTABLE SWITCHES (If Supplied)
Selectable CCT Set Correlated Color Temperature to
desired level by selecting 3KK, 4KK, or 5KK setting for each
3000K, 4000K, or 5000K CCT. (Figure 2)
2
Cooper Lighting Solutions
IB514104EN
Installation instructions
Glass Door
Assembly
Male
Connector
Figure 1.
CCT
3KK
4KK
5KK
Figure 2.
Black Plate
Female
Connector
3KK
4KK
5KK