Télécharger Imprimer la page

S+S Regeltechnik HYGRASGARD DHKF I Notice D'instruction page 6

Publicité

Les langues disponibles

Les langues disponibles

G
®
HYGRASGARD
The light-intensity sensor PHOTASGARD
The connecting head is pluggable for quick and easy mounting. The measuring transducer is accommodated in a separate housing.
The sensor used was specifically adapted to the sensitivity of the human eye. Its greatest sensitivity is in the range of 350 nm to 820 nm.
With its special filter, the sensor is therefore ideally suited to exposure measurement of daylight and/or for measuring artificial light of
high colour temperature (similar to sunlight).
It is used for daylight-dependent constant light control, to control luminaires, lighting systems, Venetian blinds and canvas blinds,
and to control light intensity and sun protection hoods to avoid unnecessary heating-up of rooms. It is used in green houses, storage halls,
industrial halls, workshops, corridors, residential and commercial buildings.
TECHNICAL DATA
Power supply:
Working resistance:
Load resistance:
Power consumption:
Sensor:
Measuring ranges:
Output:
Deviation:
Ambient temperature:
Housing:
Housing dimensions:
Cable gland:
Electrical connection:
Connecting cable:
Connecting head:
Mounting (sensor):
Protection class:
Protection type:
Standards:
PHOTASGARD
®
DHKF
Type ⁄ WG01
Measuring Range
Light Intensity (adjustable)
DHKF
D H K F I
0...500 Lux / 1 / 2 / 5 / 20 / 60 kLux
D H K F U
0...500 Lux / 1 / 2 / 5 / 20 / 60 kLux
Extra charge:
Other individual measuring ranges optional, e. g. 100 kLux
DHKF
®
DHKF with six switchable measuring ranges (six devices in one) for installation in suspended ceilings.
24 V AC (± 20 %); 15...36 V DC for U variant
15...36 V DC for I variant, depending on working resistance,
residual ripple stabilised ± 0.3 V
R
(ohm) = (U
-14 V) ⁄ 0.02 A for I variant
a
b
R
> 5 kOhm for U variant
L
< 1 W at 24 V DC; < 2 VA at 24 V AC
light sensor
multi-range switching (via DIP switches)
with 6 switchable measuring ranges
0...500 Lux ⁄ 1 kLux ⁄ 2 kLux ⁄ 5 kLux ⁄ 20 kLux ⁄ 60 kLux
(optional other individual measuring ranges, e. g. 100 kLux)
4...20 mA or 0 -10 V
typically < 5 % of final value
–30...+70 °C
plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016)
72 x 64 x 37.8 mm (Tyr 1)
M 16 x 1.5 ; including strain relief, exchangeable,
max. inner diameter 10.4 mm
2- or 3-wire (see connecting diagram),
0.14 - 1.5 mm², via terminal screws
PVC, LiY Y, 4 x 0.14 mm²,
cable length (K L) = approx. 2 m
made of plastic, material polycarbonate (PC), colour white,
pluggable, Ø = approx. 35 mm, H = approx. 29 mm
in the suspended ceiling, ceiling cut-out Ø = 30 mm,
cover Ø = < 35 mm
III (according to EN 60 730)
IP 65 (according to EN 60 529) housing only!
IP 30 (according to EN 60 529) sensor in the built-in state
CE conformity, electromagnetic compatibility according to EN 61 326,
EMC directive 2014 ⁄ 30 ⁄ EU
In-ceiling light intensity sensors
Output
Light Intensity
4 ... 20 mA
0 -10 V
Rev. 2019 - V11
Item No.
1601- 6122- 1000-000
1601- 6121-1000 -000
on request