Electrical Connections - Keyautomation 900CT-2-24S Manuel D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 21
VISUAL DIAGNOSIS
Visual diagnosis of correct connection of controls :
The control unit is designed to allow installation as quickly as possible, and thus to see immediately whether
the wiring connections are correct by means of LED indicators:
A. Red LED to indicate presence of mains power supply DL1 POWER, indicate whether the transformer is
providing power (on)
B. Red LED DL4 located at bottom right at the safety input STOP, it must be on since it indicates that the
contact is closed
C. Red LED DL3 located at lower right at the safety input Photocell Open F2 , it must be on since it
indicates that the contact is closed, when the ray of the device is interrupted, the LED must go off.
D. Red LED DL2 located at lower right at the safety input Photocell Close F1 , it must be on since it
indicates that the contact is closed, when the ray of the device is interrupted, the LED must go off.

ELECTRICAL CONNECTIONS

To ensure operator safety and to prevent damage to the components while connections are being made, or
when the radio card is being inserted, the control unit absolutely must not be powered on.
For power cords, motor lines, flasher/courtesy light line, and electric lock, use a cable with a cross-section
that is suitable for the length (minimum 1.5 mm2).
For auxiliary power supplies, controls and safety contacts a minimum section of 0.5 mm2. When the control
cables are very long (more than 30 m), de-coupling is suggested using relays at the control unit.
If a fuse trips, after removing the cause, replace it with another one of the same type. Install the various
safety devices, limit switches, photocells, sensitive rib, stop button.
If one or more of the safety devices are not installed, the corresponding terminals must be short circuited
with the controls common.
All contacts N.C. Assigned to the same input they must be connected in series.
All contacts N.O. Assigned to the same input they must be connected in parallel.
Provide disconnecting devices in the power supply network in accessible places.
For the power supply of the control unit, there must be an external disconnecting switch (not included),
independent and properly sized.
Keep the power supply cables and the encoder cables separate with a distance motor-control unit with a
maximum of 10 metres. Do not use multi-pole cables.
-
Operation of motor M1 :
Connected to Term. N.6 and Term. N.7
-
Operation of motor M2 : Connected between Term. N.8 and Term. N.9
Motor M2 starts first during closing
-
Operation of electric lock output ELS
Connected between Term. N.10 and Term. N.11
At the opening command, it comes on for1 sec. Before activating door M1
-
Operation of flasher:
Connected to Term. N.11and Term.N.12 Max. power 25W 24V.
In both opening and closing, there is a pre-flash of 1.5 sec. to inform the user that the automation
activates a movement.
-
Phototest operation power supply of TX photocells
If you want to carry out the phototest cycle at each opening, insert Dip 8 = ON and connect the
NEGATIVE power supply of the photocell transmitter device to connector no. 13
24V
min.2x1.5mm
Encoder
min.3x0.5 mm
16
2
2