HOW FUMEREX WORKS: ALARM NOTIFICATION
A
In the event of smoke/CO detection, the system will cause an alarm and can notify the listed user
phone number by SMS text message.
In the event of alarm, the system will follow this pattern:
The system switches to Wake-Up mode (see SLEEP AND WAKE-UP MODES).
The system attempts to send an SMS text message containing alarm text to all listed user
phone numbers simultaneously.
The system auto-resets the smoke or CO detector when the smoke/CO clears. The system will
not extend the Wake-Up mode period nor deliver any extra SMS text message in case of alarm
recurrence while the Wake-Up mode period is in progress.
The system may fail to deliver the SMS text message to the listed user phone number due to
the following reasons:
system or user's phone has been out of GSM signal coverage.
user's mobile phone has been switched off.
The system sends the SMS text message only once and in case of all unsuccessful attempts
within a Wake-Up period, the system will switch to Sleep mode and erase the alarm event
from the memory.
CO related SMS text messages and device indications:
CO critical level 1 – when CO concentration 30-49ppm remains for more than 120 minutes.
This level causes no audible alarm.
CO critical level 2 – when CO concentration 50-99ppm remains for more than 60 minutes.
Indicated by a 2-second beep every 5 seconds and red indicator flash.
CO critical level 3 – when CO concentration 100-299ppm remains for more than 10 minutes.
Indicated by a 2-second beep every 5 seconds and red indicator flash.
CO critical level 4 – when CO concentration 300ppm and more are reached. Indicated by a
2-second beep every 5 seconds and red indicator flash.
Fresh air – when CO level decreases from any critical level to 0-29ppm. This level causes no
audible alarm.
CO sensor ERROR – CO sensor has failed. Please contact your local supplier for repair service.
CO sensor lifetime is 7 years.