Dip Switch Position - Lenze E82ZAFSC Instructions De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

DIP switch position

ON
1
2
3
4
)
Note!
Make sure to set the DIP switch and C0034 to the same range, otherwise
ƒ
the analog input signal at X3/8 will be interpreted incorrectly by the basic
device.
If a setpoint potentionmeter is supplied internally via X3/9, make sure to
ƒ
set the DIP switch to the voltage range 0 ... 5 V. Otherwise it will be
impossible to cover the entire speed range.
Signal at X3/8
0 ... 5V
0 ... 10 V (Lenze setting)
0 ... 20 mA
4 ... 20 mA
4 ... 20 mA (open−circuit monitored)
−10 ... +10 V
EDK82ZAFSC DE/EN/FR 5.0
5
1
OFF
OFF
OFF
OFF
OFF
ON
l
Commissioning
DIP switch position
ON
OFF
Switch position
2
3
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
C0034
4
5
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
7
0
0
0
1
3
2
41

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

E82zafsc001Standard-i/o

Table des Matières