Install To Fit Your Application; Electrical Requirements - Honeywell Home DR65A3000 Guide D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Install to Fit Your Application

Flex duct is recommended in connecting to the DR65A3000 collars to reduce vibration noise.
Dedicated Return to Main Supply
A
RETURN
SEPARATE
RETURN
Main Return to Main Supply
B
RETURN
DR65A3000 Dehumidification System 33-00297EFS—09
AIR HANDLER
SUPPLY
DEHUMIDIFIER
(OPTIONAL)
GRAVITY DAMPER
BACKDRAFT
DAMPER
AIR HANDLER
SUPPLY
DEHUMIDIFIER
BACKDRAFT
DAMPER
Duct Sizing: Use minimum 8" diameter round for duct
lengths up to 25' Minimum 10" required for lengths
longer than 25' Duct branches from the main inlet/
exhaust should be minimum 8" round for 2-3 branch-
es, and 8" round or larger for 4 branches or more.
Isolated Areas: Effective dehumidification may
require ducting to isolated or stagnant air flow areas.

Electrical requirements:

115 VAC outlet. Ground fault
interrupter (GFI) recommended.
Ideal when...
Access to a dedicated central return for
DR65A3000 is available.
Combined with A/C operation; requires
backdraft damper on the exhaust
port to minimize backdraft when
DR65A3000 is not on but A/C is.
Providing dry air to a specific area with
M36843
an optional 20% open gravity damper
on DR65A3000 supply.
Ideal when...
Running DR65A3000 when not running
A/C.
Requires damper on the exhaust port to
minimize backdraft when DR65A3000
is not on but A/C is.
Access to a dedicated central return for
DR65A3000 is not available.
System fan should run with
M36844
dehumidifier for best results.
M24745
5

Publicité

Table des Matières
loading

Table des Matières