flame for this purpose but a non-corrosive substance such as soapy water or phoamy substances as contained in leak-
finder sprays. All our appliances undergo careful testing: the type of gas, the operating pressure and the category are
indicated on the data plate.
The appliances must be checked in such a way as to verify that the heat output is correct:
•
The heat output (thermal power) is indicated on the data plate of the appliance.
•
Firstly, check that the appliance can be used with the type of gas supplied; then check that the indication on the
plate corresponds to the gas to be used. For converting to another type of gas, check that the type of gas complies
with what is stated in this instruction manual.
The pressure must be read by inserting a gauge for liquids (e.g. a U gauge). With a minimum definition of 0,1 mbar,
into the relative pressure outlet (see fig. B position C).
Remove the screw from the airtight pressure outlet, connect the rubber pipe of the U gauge and read the pressure.
After reading, remove the flexible pipe of the gauge, put back the screw, tighten hermetically and check the pressure
tightness.
Connection for liquid gas G30/G31
The connection pressure for liquid gas is 30 mbar with butane and 37 mbar with propane.
Check the plate, read the pressure and verify that the description of the nozzle installed corresponds to the one supplied
by the manufacturer.
Connection with methane gas H G20
The connection pressure for methane gas is 20 mbar.
Check the plate, read the pressure and verify that the description of the nozzle installed corresponds to the one supplied
by the manufacturer.
CHECKING PRIMARY AIR TO THE MAIN BURNERS AND PILOT NOZZLES
All the burners are fitted with an air regulator by means of which the primary air can be varied thanks to an adjustable
bush that can be locked with a screw. In the "Burner Technical Data" table you will find the approximate values for the
"h" parameter (primary air). The flow of primary air must be regulated so there is no detachment of the flame when the
burner is cold or a return of the flame when the burner is hot.
The pilot air is regulated when the appliance is tested and inspected for the gas it is set for.
If you are going to change to a different type of gas, regulate the air by means of the adjusting bush until the flame stops
sputtering and becomes an intense blue colour.
Burner 6,95 kW min. 2,69 kW
Burner injector 1/100 mm
Min. output adjustment 1/100 mm
Pilot Injector 1/100 mm
Consumption
Primary air h=mm
Burner 13,9 kW min. 5,15 kW
Burner injector 1/100 mm
Min. output adjustment 1/100 mm
Pilot Injector 1/100 mm
Consumption
Primary air h=mm
DISPOSALS FOR CONVERTING AND INSTALLING FOR OTHER TYPES OF GAS
Our appliances are tested and regulated with liquid gas /see plate).
GB
CHECKING HEAT OUTPUT
TABLE OF "BURNERS" TECHINCAL DATA
12.8 kWh/KG
G30
BUTANE
28 mbar
130A
kg/h 0,548
190A
kg/h 1,096
open
IE
12.8 kWh/KG
G31
PROPANE
37 mbar
130A
85
85
30
30
kg/h 0,540
25
25
190A
125
125
30
30
kg/h 1,080
open
28
3
9.45 kWh/m
st.
G20
NATURAL GAS
20 mbar
205A
adjustable
51
3
m
st./h 0,735
25
300A
adjustable
51
kg/h 1,471
25