MAINTENANCE
At the end of the heating season, it is good practice to clean the filter, the combustion head (disk, insulator,
electrodes, nozzles, the combustion air passage and the photoresistant cell. It is advisable to use wood or plastic
instruments to clean the nozzle passages. Nozzles should be replaced after 12 months' use.
Most components can be inspected by removing the hood. To inspect the head you must disassemble the component-carrying
plate which can be hung on hung on the burner body in two different positions to make work as practical as possible. The
motor, transformer and solenoid valve are connected via a connector while the photo-resistor is push-locked into place.
24
TWO STAGE LIGHT OIL BURNERS
1) Undo the lid screw "A" to gain access to the
interior of the burner.
2) Undo the 6 screws "B" of the plate, as indicated, in
order to access nozzle, electrodes and fun.
3) The plate must be hung up as illustrated in fig. C.
4) The deflector disk can be removed by
loosening the screw "C".
N° 0002934140
Rev. 30/03/2004