5.3 What is in the box
5.4 Diffuser Installation
When fitting the diffuser near a smoke alarm the blanking plates provided must be fitted to avoid blowing air over the smoke
alarm and affecting its operation. If the unit is installed in a dwelling 3 storeys or above, it should be linked to a smoke alarm
in such a way that power is removed from the unit if the smoke alarm is activated. Our standard diffuser is not suitable for
installation in 3 storey or above homes or fire protected areas.
In case of installation of the AIRQURE P1-H model (with heating element) the flexible duct should be the shortest possible.
Alternatively use a thermal insulated duct (accessory on request).
Fig. 5.a
Fig. 5.c
5.5 Ceiling installation
The unit must be installed in the following position.
Spirit level
Fig. 5.e
5.e Prepare the surface where the unit is to be mounted. Make sure that the surface is flat, leveled and that it supports the weight
of the unit. Perform the installation in accordance with local rules and regulations.
5.f Use appropriate screws (not supplied) to fix the unit to the ceiling. It is recommended to fit the unit with anti-vibration mounts
(not supplied).
1. Ventilation unit
4. Manual
2. Pre-Filter
5. Diffuser
3. Duct
6. Screws + wall plugs
7. 2x Metal clamps
8. 2x Mylar flap
Fig. 5.b
Fig 5.d
Fig. 5.f