Continuity Loop Test - LEM HEME GEO 30 Manuel D'utilisation

Appareil de test de boucle de terre
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

4

Continuity Loop Test

The testing procedures are the same as ground resistance measurement:
Open the jaws and make sure the jaw mating surfaces are clean and free of
dust, dirt or any foreign substances.
Snap (open and close) the jaws a few times to ensure the jaws mate properly.
Turn the power on, and set the rotary switch to the "Continuity" position.
Do not clamp on to any conductor or open the jaws at this moment or
during self-calibration.
At powering on, the clamp-on ground tester will self-calibrate for better accuracy.
Users should wait for the self-calibration to finish before making measurements.
During the self-calibration, the LCD will show CAL7, CAL6,..., CAL2, CAL1.
When the ground tester is ready, a beep sound will be heard.
Clamp on to the electrode or ground rod to be measured.
A beep sound will be heard if resistance R g is less than 40 Ω.
HEME GEO 30
SO8130Z Rev. B
R
g
Continuity Loop Test
11

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Se 8130 z

Table des Matières