Programme closing
Finish the programming mode
1 Place DIP1 and DIP2 in "OFF".
DL3 will remain off.
The runs for the leaves both in opening and
closing will be memorised.
The positions in which the leaf begins to slow
down, both on opening and in closing, are also
memorised (with DIP8=ON only).
5
PEDESTRIAN OPEN/CLOSE PROGRAMMING
Programming the pedestrian open/close of the gate is done using the ST2 mini-push button, the pedestrian
operation device (A.P.) or the transmitter.
The programming of the total open/close must be complete.
If the gate collides with an obstacle during programming, repeat the programming process.
Before making the programming, ensure there is no person, animal or object in the radius of action of
the gate and the mechanism.
PROGRAMMING AND STARTUP
1 Start closing of leaf 2: press ST1; leaf 2 begins to
close.
2 Start soft stop on closing of leaf 2 (with
DIP8=ON only): press ST1 at the point chosen for
the start of deceleration (DC2) (except in hydraulic
operators).
3 Finish closing of leaf 2: press ST1 in leaf 2 closed
position.
4 Start closing of leaf 1: press ST1; leaf 1 begins to
close.
5 Start soft stop in closing of leaf 1 (with DIP8=ON
only): press ST1 at the point chosen for the start of
deceleration (DC1) (except in hydraulic operators).
6 Finish closing of leaf 1: press ST1 in leaf 1 closed
position.
When using the control board with a single operator
(operator A1, see Fig. 3 on page 29), the times
corresponding to operator A2 must be zero. To do
this, instead of carrying out steps 1, 2 and 3, press
ST1
three
times
consecutively
DIP8=OFF).
(twice
with
Control board VIVO-M201(M)
35