Schéma D'interconnexion De La Sonde Xpp-5 - Siemens MFA 4p Instructions De Service

Détecteurs de mouvement
Table des Matières

Publicité

4.2.5
Schéma d'interconnexion de la sonde XPP-5
NOTES :
Milltronics MFA 4p
Instructions de service, 12/2020, A5E34001305-AC
NON - HAZARDOUS LOCATION
MILLTRONICS
CONTROLLER
MILLTRONICS
CONTROLLER
1) THE XPP-5 CABLE MUST BE TERMINATED IN AN AREA EXTERNAL
TO HAZARDOUS LOCATIONS, CLASS I, DIV 1, GR. A,B,C,D & CLASS II, DIV 1, GR. E,F,G.
2) A SEAL SHALL BE INSTALLED WITHIN 50 mm OF THE XPP-5 CONDUIT HUB
FOR CLASS I, DIV. 1 HAZARDOUS LOCATION ONLY.
3) INSTALLATION SHALL BE DONE IN ACCORDANCE WITH
CANADIAN ELECTRICAL CODE PART 1 REQUIREMENTS.
4) DO NOT EXPOSE THE XPP-5 TO DIRECT SUNLIGHT, OTHERWISE
PROVIDE SUN SHIELD.
5) STATIC HAZARD, DO NOT RUB WITH DRY CLOTH.
N. T. S.
B. GRAY
R. CLOSS
INTERCONNECTION DIAGRAM
S. NGUYEN
HAZARDOUS LOCATION
CLASS I, DIV 1, GROUPS A,B,C,D
CLASS II, DIV 1, GROUPS E,F,G
METAL CONDUIT
CERTIFIED
CERTIFIED
CONDUIT
CONDUIT
SEAL
SEAL
FITTING
FITTING
JUNCTION BOX
CLASS I & II
METAL CONDUIT
CERTIFIED
CONDUIT
SEAL
FITTING
2
1
0
XPP-5
2365013102
4.2 Interconnexions
CERTIFIED
CONDUIT
SEAL
FITTING
REVISED HOUSING THREADS
RWG
SN
PER ECN #00-000-0-0070
REVISED CABLE AND TERMINAL CONNECTOR
RWG
SN
PER ECN #00-000-0-0037
RWG
SN
FOR CONSTRUCTION
23650131
1=1
1
1
Raccordement
JULY
11/00
APRIL
18/00
MARCH
27/00
2
17