8

Diagnostics

LED status displays

8
Diagnostics
LED status displays
E82ZAFPC010
LED
Pos.
Colour
yellow
green
yellow/

+
green
70
1
2
Condition
Description
off
No communication with the PROFIBUS master.
blinking
Communication with the PROFIBUS master has been established
via the function module.
off
The function module is not supplied with voltage.
The standard device and/or the external voltage supply is
switched off.
blinking
The function module is supplied with voltage but is not connected
to the standard device.
Causes:
The standard device is switched off.
The standard device is in the initialisation phase.
The standard device is not available
on
The function module is supplied with voltage and is connected to
the standard device.
blinking
Internal function module error
E82ZAFP016