Step
Procedure
4.
Make other necessary controller settings.
W Commissioning of the controller
l
For initial commissioning set code C0005 = 1003 (signal
configuration: speed control via AIF).
l
Enable the controller.
– Terminals SI1 ( controller enable) and SI2 (pulse inhibit) are
always active and have to be HIGH during operation.
Otherwise the controller will be inhibited.
Note
The controller must always be externally supplied with 24 V DC.
EDKMF2102 DE/EN/FR 8.0
Commissioning for ECS series standard devices
l
Commissioning
Detailed
information
Documentation
for the respective
controller
7