Electrical Connection; Electrical Installation - Dimplex SI 22TU Instructions D'installation Et D'utilisation

Pompe à chaleur eau glycolée-eau pour installation intérieure
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

SI 22TU

7.5 Electrical connection

7.5.1 General
All electrical connection work must be carried out by a trained
electrician or a specialist for the specified tasks in accordance
with the
installation and operating instructions,
country-specific installation regulations (e.g. VDE 0100),
technical connection conditions of the energy suppliers and
supply grid operators (e.g. TAB) and
local conditions.
To ensure that the frost protection function of the heat pump
works properly, the heat pump manager must remain connected
to the power supply and the flow must be maintained through the
heat pump at all times.
The switching contacts of the output relay are interference-sup-
pressed. Therefore, depending on the internal resistance of the
measuring instrument, a voltage can also be measured when the
contacts are open. However, this will be much lower than the line
voltage.
Extra-low voltage is connected to controller terminals N1-J1 to
N1-J11; N1-J19; N1-J20; N1-J23 to N1-J26 and terminal strip
X3. If, due to a wiring error, the line voltage is mistakenly con-
nected to these terminals, the heat pump manager will be de-
stroyed

7.5.2 Electrical installation

1)
The electric supply cable for the output section of the heat
pump (up to 5-core) is fed from the electricity meter of the
heat pump via the utility blocking contactor (if required) into
the heat pump Connection of the mains cable to the control
panel of the heat pump via terminal X1: L1/L2/L3/PE.
An all-pole disconnecting device with a contact gap of at
least 3 mm (e.g. utility blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping for
all external conductors must be installed in the power supply
for the heat pump (tripping current and characteristic in com-
pliance with the device information).
ATTENTION!
Ensure the rotary field is clockwise when connecting the mains cables (if
the rotary field is not clockwise, the heat pump will not work properly, is
very loud and may cause damage to the compressor).
2)
The three-core electric supply cable for the heat pump man-
ager (heating controller N1) is fed into the heat pump .
Connection of the control line to the control panel of the heat
pump via terminal X2: L/N/PE.
Details on the power consumption of the heat pump are
listed on both the product information sheet and the type
plate.
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump
manager must have a constant voltage. For this reason, it
should be tapped upstream from the utility blocking contac-
tor or be connected to the household current, as important
protection functions could otherwise be lost during a utility
block.
EN-8
3)
The utility blocking contactor (K22) with 3 main contacts (1/
3/5 // 2/4/6) and an auxiliary contact (NO contact 13/14)
should be dimensioned according to the heat pump output
and must be supplied by the customer.
The NO contact of the utility blocking contactor (13/14) is
looped from terminal strip X3/G to connector terminal X3/A1.
CAUTION! Extra-low voltage!
4)
The contactor (K20) for the immersion heater (E10) of mono
energy systems (HG2) should be dimensioned according to
the radiator output and must be supplied by the customer. It
is controlled (230 V AC) by the heat pump manager via ter-
minals X2/N and X2/K20.
5)
The contactor (K21) for the flange heater (E9) in the hot
water cylinder should be dimensioned according to the radi-
ator output and must be supplied by the customer. It is con-
trolled (230 V AC) by the heat pump manager via terminals
X2/N and X2/K21.
6)
The contactors mentioned above in points 3, 4 and 5 are in-
stalled in the electrical distribution system. Mains cables for
the installed heaters must be laid and secured in accord-
ance with the valid standards and regulations.
7)
All installed electric cables must have permanent wiring.
8)
The heat circulating pump (M13) is activated via the contact
N1-J13/NO5. The connection points for the pump are
X2/M13 and X2/N. When using pumps where the switching
capacity exceeds the output, a coupling relay must be inter-
posed.
9)
The auxiliary circulating pump (M16) is activated via the con-
tact N1-J16/NO9. The connection points for the pump are
X2/M16 and X2/N. When using pumps where the switching
capacity exceeds the output, a coupling relay must be inter-
posed.
10) The domestic hot water circulating pump (M18) is activated
via the contact N1-J13/NO6. The connection points for the
pump are X2/M13 and X2/N. When using pumps where the
switching capacity exceeds the output, a coupling relay must
be interposed.
11) The brine or well pump (M11) is activated via the contact N1-
J12/NO3. The connection points for the pump are X2/M11
and X2/N. When using pumps where the switching capacity
exceeds the output, a coupling relay must be interposed.
12) The return flow sensor is integrated into the heat pumps
and is connected to the heat pump manager via the control
line. The return flow sensor must be installed in the im-
mersion sleeve in the manifold only when a dual differen-
tial pressureless manifold is used. The single-core wires are
then connected to terminals X3/GND and X3/ R2.1. Bridge
A-R2 (situated between X3/B2 and X3/1 when delivered)
must then be moved to terminals X3/1 and X3/2.
13) The external sensor (R1) is connected to terminals X3/GND
and X3/R1.
14) The domestic hot water sensor (R3) is included with the do-
mestic hot water cylinder and is connected to terminals X3/
GND and X3/R3.
452235.66.01 · FD 9310
www.dimplex.de

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

452235.66.01

Table des Matières