Electrical Connections; Important; Warnings; Details On Installation In The Bathroom - Fondital MANIVA 3110 Manuel D'installation

Radiateurs électriques à fluide caloporteur
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

2.

ELECTRICAL CONNECTIONS

IMPORTANT

During installation, maintenance and cleaning, the appliance must not be powered.
The appliance must be powered only with 230 Vac voltage. The radiator has 3 cables as per the table below :
Brown
Blue or Gray
Black
WARNING
The Pilot Wire is intended for radiators sold in France. If the black "pilot wire" is not used, safety standards impose to insulate it
and not to connect it for any reason to the ground wire.
It is compulsory to install a multipolar switching device. The minimum separation distance between contacts shall be at least 3 mm.
It is compulsory that the power supply circuit of the appliance is protected by a high sensitivity differential protection device.
Do not introduce and do not try to penetrate with metal objects into the side of the radiator containing the adjustment electrical system
(right side).
If the power cable is damaged, it must be replaced only by a qualified electrician.

2.1 Details on installation in the bathroom

Installation must be compliant with the standards and laws in force in the country of installation. The radiator is in class II and with IP24
electrical protection. In the bathroom, it can be installed in areas 2 and 3 (see figure no.1) only if the control device cannot be touched by
people that are using the shower or the bath.
Radiator mustn't be connected to the earth wire.
In the bathroom, protect the power line with a high sensitivity 30 mA differential protection device
Install a multipolar switching device. The minimum separation distance between contacts shall be at least 3 mm.
3.

INSTALLATION OF THE APPLIANCE

PTo achieve the best results in terms of heat output and comfort of your appliance, we recommend to install the radiator, if possible, under
a window or near areas with high heat loss of the room to heat.
The radiator must not be installed in a recess or under a power outlet.
Curtains, furniture or other objects that may obstruct the correct heat distribution must be placed at a minimum distance of 500 mm from
the front of the radiator.
Respect a distance of at least 120 mm from the lower edge of the radiator and the floor and al least 300 mm from a possible shelf.
EN-22
Phase
Neutral
Pilot wire
ZONE 0
ZONE 1
ZONE 0
ZONE 2
ZONE 3
fig. 1
2,25 m