Mettler Toledo IND560 PDX Guide D'installation page 59

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Relay Outputs
The relay outputs can switch up to 250 VAC or 30 VDC voltages at 1A maximum.
The relay outputs are not polarity-sensitive since they are dry contact outputs. An
example of wiring to the outputs is given in Figure 2-46.
Allen-Bradley RIO
Connections to the A-B RIO option board (Figure 2-47) are made using a three-pin
terminal connector on the RIO option.
Figure 2-47: A-B RIO Option Board
IND560 PDX Installation Manual
NOTES:
1. DRY CONTACT RELAYS.
2. RELAY CONTACT RATING:
AC: 24-280 VAC, 1.0 AMP. INTO RESISTIVE
LOAD
DC: 5-24 VDC, 1.0 AMP. INTO RESISTIVE LOAD.
MAXIMUM SWITCHING POWER: 250VA, 30 W.
3. MAXIMUM OUTPUT CIRCUIT CURRENT = 3
AMPS.
4. ALL INDUCTIVE LOADS MUST BE SUPPRESSED.
5. WIRE SIZE: 14 AWG (2.088 mm
Figure 2-46: Relay Outputs
2
) MAXIMUM
2
22 AWG (0.322 mm
) MINIMUM.
2-29

Publicité

Table des Matières
loading

Table des Matières