Optional EM Mounting (Steps 1-4)
1.
EM UNIT - Install EM unit into existing fixture channel.
EM unit should be mounted so that there is sufficient
cable length to make all connections to LED driver and
EM test switch. Mount EM unit on the opposite end of
the channel, so it will not interfere with the driver that
is attached to the gear tray. (Figure 6.)
TEK Screw
Figure 6.
2.
Wiring – Remove accessory bracket before installing
the gear tray (Figure 7 .) Hang SSRK Gear tray to allow
for wiring (Figure 8.), make the connection between
EM unit and LED Driver. Route the EM unit test switch
wire to end of gear tray with slots at the end, feed the
wire though a socket track hole if applicable. When
mating the gear tray to the channel, guide the EM test
switch wire through the corresponding slot on the gear
tray to make sure the EM wire is accessible to connect
to the EM test switch.
Accessory
Bracket
TEK Screw
Figure 7.
Installation Instructions – Surface Strip Retrofit Kit (SSRK)
Emergency
Battery
(EL7/EL14)
Figure 8.
Existing
3.
Channel
TEK Screw
Gear Tray
Figure 9.
4.
COOPER LIGHTING SOLUTIONS
LED Driver
EM Connectors
Connect the EM unit white cable connector to the test
switch and then reinstall the accessory bracket, making
sure the cable is inside of the accessory bracket
(Figure 9). Wire incoming power connections (ensure
power is off).
EM Test Swtich
Electical
Connection
Install Lens if applicable, then power the unit and test
functionality of all components, do not remove RED
Stop sign on EM Test Switch until power is applied
to the charging circuit of EM Unit to prevent battery
discharge.