The wiring requires the shielded power cable 12Vdc (ex. 2x0.5 mm
connected to ground to prevent the introduction of disturbances of the alternating voltage on the barrier.
The cable size depends on the consumption of the barriers and the resistance of the cable.
The table shows the cable cross-sections and the relative distances to ensure optimal performance using a
power supply and a barrier.
DS1033-135A
SIZE CONDUCTOR
0,5 mm²
0,75 mm²
1,5 mm²
2,5 mm²
2
+ 8x0.22 mm

POWER SUPPLY

12Vcc
165 m
245 m
490 m
820 m
2
) with the metallic shield