Electrical connection
The electrical connections must be made in compliance with the provisions of DIN VDE 0100 T1 and
T702 by a qualified electrician. The units must be permanently installed outside the protected area in
a dry place (shaft or min. 3.5m from the edge of the pool).
The circuit is wired ready for connections, the connections are made in accordance with the wiring
diagram.
1. With the three-phase motor 3~, the power consumption of the pump motor is approx. P
With the ac motor 1~, the power consumption is approx. P
2. The motor protection relay must be set to the rated current stated on the motor rating plate.
3. On commissioning, the direction of rotation must be checked (three-phase only). If the direction of
rotation is wrong, swap the phases.
4. Connect the pneumatic button control hose to the end of the hose on the control box.
Existing connection
1. GFCI, I
= 30mA
ΔN
2. Fuse 1~ 230 V / 3~ 400 V cutout 20 A / 16 A slow, or 20 A / 16 A K-circuit breakers
3. All-pole switching switch designated 0 and 1
4. A connection for equipotential bonding, which is attached to the earthing strip, must be provided.
Further information can be found on the connection diagram.
These parts are not supplied as standard and must be provided by the customer prior to the unit
being installed.
40
29.04.2013 TB-b bta_bj_vogue_wave_engl_29042013.indd
2.89 kW.
1
3.18 kW.
1