Venting Requirements - Whirlpool GZ5730XR Série Instructions D'installation Et Guide D'utilisation Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Venting Requirements

Vent system (if needed) for installation is not included.
Vent system must terminate to the outdoors, except for non-
vented (recirculating) installations.
Do not terminate the vent system in an attic or other enclosed
area.
Do not use 4" (10.2 cm) laundry-type wall caps.
Use metal vent only. Rigid metal vent is recommended. Do
not use plastic or metal foil vent.
For the most efficient and quiet operation:
The length of vent system and number of elbows should be
kept to a minimum to provide efficient performance. The size
of the vent system should be uniform.
Do not install 2 elbows together.
Vent system can terminate either through the roof or wall.
For the most efficient and quiet operation, it is recommended
that the range be vented vertically through the roof through
7" (17.8 cm) round vent system.
Use vent clamps to seal all joints in the vent system.
Use caulking to seal exterior wall or roof opening around the
cap.
Venting Methods
Determine which outside venting method needs to be used. It is
recommended that the vent system be installed before installing
the range hood.
NOTE: If a non-vented (recirculating) installation is desired, follow
instructions in the "Make Electrical Connection" section.
Roof Venting
A
D
B
C
A. 7" (17.8 cm) round vent or a
3¹⁄₄" x 10" (8.3 x 25.4 cm) vent
through roof
B. Round vent: use 7" (17.8 cm)
round damper
(purchased separately)
C. 18" (45.7 cm) - 24" (61.0 cm)
above cooking surface
D. Roof cap
Wall Venting
A
B
D
C
A. 7" (17.8 cm) round vent or a
3¹⁄₄" x 10" (8.3 x 25.4 cm) vent
through the wall
B. 3¹⁄₄" x 10" (8.3 x 25.4 cm)
through the wall
C. 18" (45.7 cm) - 24" (61.0 cm)
above cooking surface
D. Wall cap
Calculating Vent System Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
Use 3¹⁄₄" x 10" (8.3 cm x 25.4 cm) or 7" (17.8 cm) round vent with
a maximum length of 65 ft (19.8 m) for vent system. For best
performance, use no more than three 90° elbows. To calculate
the length of system you need, add the equivalent feet for each
vent piece used in the system. See the following examples.
3¹⁄₄" x 10" (8.3 cm x 25.4 cm) Vent System
Vent Piece
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
90° elbow
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
flat elbow
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
wall cap
Example vent system
¹⁄₄
3
" x 10"
(8.3 x 25.4 cm)
elbow
6 ft (1.8 m)
2 ft
(0.6 m)
Maximum Recommended Length
1 - 90° elbow
8 ft (2.4 m) straight
1 - wall cap
Length of 3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
system
3¹⁄₄" x 10" (8.3 cm x 25.4cm)
Round
5.0 ft
(1.5 m)
12.0 ft
(3.7 m)
0.0 ft
(0.0 m)
Wall cap
= 35 ft (10.7 m)
= 5.0 ft (1.5 m)
= 8.0 ft (2.4 m)
= 0.0 ft (0.0 m)
= 13.0 ft (3.9 m)
5

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Gz5736xr série

Table des Matières